Copyright © RTW Engineering 2004 / 2007 Portions copyright Insulmastic.
  
NoSprayNoSpray
NoSprayNoSpray

NoSpray® Protection System

NoSpray® Protection System is a type approved aluminum/glass cloth jacketing system designed to prevent the flammable spray of hot oil which can come in contact with hot surfaces thus causing fires in vessel engine rooms.

NoSpray® is available in tape or sheet format and is coated on one side with a silicone adhesive for ease of installation and superior adhesion.

Meets SOLAS Regulation II - 2/15.2.11

Applications

For Protection of Insulated High Temperature Surfaces

NoSpray can be used as a protective shield on insulated hot surfaces which are in close proximity to potential oil spray in the engine room.

 

The areas of fire risk listed on the left should be protected from the sources of ignition listed on the right:

Fuel oil injection pipes, fuel oil service pipes, fuel oil valve cooling oil pipes attached to diesel engines
Lube oil service pipes and hydraulic oil pipes attached to diesel engines
Flammable oil pipes
Flammable oil pump and strainer
Fuel oil heater
Lube oil heater and cooler
Fuel oil purifier - Lube oil purifier
Fuel oil burning unit for boiler, thermal oil heater, inert gas generator and incinerator
Level gauge, fittings and oil tray of flammable oil tank
exhaust gas pipe
steam pipe
turbo charger
electrical equipment
boiler, thermal oil heater, incinerator
welding spatter, cigarettes, etc.

 

 

 

NoSpray ApplicationNospray Application
1.) Be sure that all surfaces to be protected are cleaned and free of oil.
 
2.)
Select the NoSpray format applicable to your installation, and, with adhesive film in place, cut with scissors as follows:
 
For Pipes and Joints:
Use NoSpray Tape and allow overlap of 50% each turn.
 
For Valves, Flanges, and other irregular shaped equipment:
Use NoSpray Sheet and cut a to size as follows:
 
Length: 

 
to wrap 2 layers thick around surface to be protected.
Width:  
to be enough to completely cover bolts and overlap onto connecting pipe at least 100 mm (4”).

 

Special care must be taken where a device such as a valve is connected to the pipe being wrapped. In this case, the NoSpray Tape must be wrapped around the attached device as well as the pipe.

When using NoSpray Sheet, apply NoSpray Tape on top of the sheet overlapping 50% to secure the NoSpray Sheet.

3.)
Important Tip
When applying NoSpray Tape, be sure to wrap loosely to allow free flow of oil leak. DO NOT WRAP TIGHTLY.
 
4.)
When applying NoSpray Sheet or Tape, peel off the adhesive film a little at a time so as not to contaminate adhesive surface with dust or oil prior to application. Wrap snugly (not too tight) around pipe or joint in the likely direction of an oil spray leak. NoSpray Sheet or Tape should be continued to a point where any potential leaks would occur safely away from hot surfaces that could cause combustion.
 
5.)
For maintenance and repairs, NoSpray can be removed by cutting with a knife, or tearing with pliers. NoSpray cannot be reused once removed.
 

Important Note

Periodic inspections must be carried out in areas applied with NoSpray Tape. Unravelling, curling, loosening or cracking indicates tape on the applied area must be replaced.

Application Instructions

 